Drive exception/fault behavior, Drive exception/fault, Behavior – Rockwell Automation 2094-EN02D-M01-Sx Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drives User Manual User Manual

Page 217: Tabl

Advertising
background image

Rockwell Automation Publication 2094-UM002E-EN-P - May 2012

217

Troubleshooting the Kinetix 6200 and Kinetix 6500 Drive System

Chapter 8

Drive Exception/Fault Behavior

Table 101 - Drive Behavior, FLT Sxx Fault Codes

Four-character Display Message

RSLogix 5000 Fault
Message

Description

CIP Motion
Exception Behavior

Sercos Fault
Behavior

FLT S02…MTR COMMUTATION

Illegal Hall State

The motor encoder Hall inputs are all high or all low.

Coast/Disable

Coast/Disable

FLT S03…MTR OVERSPEED FL

Motor Overspeed

The motor speed has exceeded 125% of the motor maximum
speed ratings.

Coast/Disable

Coast/Disable

FLT S04…MTR OVERSPEED UL
(Kinetix 6500 drives only)

Motor Overspeed

Motor speed has exceeded 125% of maximum rated speed. The
100% trip point is dictated by the lesser of the user velocity
limits or the motor rated base speed.

Decel/Hold

N/A

FLT S05…MTR OVERTEMP FL nn

Motor
Overtemperature

The motor thermostat, motor thermistor, or encoder
temperature sensor indicates that the motor factory
temperature limit has been exceeded. The nn sub-code is
defined as follows:
01: Motor Thermostat or Thermistor.

02: Encoder Temperature Sensor.

Coast/Disable

Coast/Disable

FLT S06…MTR OVERTEMP UL nn
(Kinetix 6500 drives only)

Motor
Overtemperature

Decel/Hold

N/A

FLT S07…MTR OVERLOAD FL

Motor Thermal
Protection

The thermal model for the motor indicates that the
temperature has exceeded 110% of its rating.

Decel/Disable

Decel/Disable

FLT S08…MTR OVERLOAD UL
(Kinetix 6500 drives only)

Motor Thermal
Protection

The thermal model for the motor indicates that the
temperature has exceeded a user programmable limit.

Decel/Hold

N/A

FLT S10…INV OVERCURRENT

IPM Fault

The IPM fault output indicates that the power transistors were
turned off because of overcurrent, overtemperature, or power
supply problems.

Coast/Disable (open
contactor enable relay)

Coast/Disable (open
contactor enable relay)

FLT S11…INV OVERTEMP FL

Inverter
Overtemperature

The inverter temperature has exceeded its limit.

Coast/Disable (open
contactor enable relay)

Coast/Disable (open
contactor enable relay)

FLT S13…INV OVERLOAD FL

Inverter Thermal
Protection

The thermal model for the power transistors indicates that the
temperature has exceeded 110% of its rating.

Coast/Disable

Coast/Disable

FLT S14…INV OVERLOAD UL
(Kinetix 6500 drives only)

Inverter Thermal
Protection

The thermal model for the power transistors indicates that the
temperature has exceeded the user-programable limit.

Decel/Hold

N/A

FLT S16…GROUND CURRENT

Ground Fault

Excessive ground current was detected in the converter.

Coast/Disable (open
contactor enable relay)

Coast/Disable (open
contactor enable relay)

FLT S18…CONV OVERTEMP FL

Converter
Overtemperature

The converter temperature has exceeded its limit.

Coast/Disable (open
contactor enable relay)

Coast/Disable (open
contactor enable relay)

FLT S20…CONV OVERLOAD FL

Converter Thermal
Protection

The thermal model for the converter indicates that the
temperature has exceeded its rating.

Coast/Disable (open
contactor enable relay)

Coast/Disable (open
contactor enable relay)

FLT S21…CONV OVERLOAD UL
(Kinetix 6500 drives only)

Converter Thermal
Protection

The thermal model for the converter indicates that the
temperature has exceeded a user-programmable limit.

Decel/Hold

N/A

FLT S22…AC POWER LOSS

AC Power Loss

All three AC input phases are detected as absent when an axis is
enabled.

Coast/Disable

Decel/Disable

FLT S23…AC PHASE LOSS nn

AC Phase Loss

Some, but not all AC input phases are detected as absent. The
nn sub-code is defined as follows:
01: L1 is missing.

02: L2 is missing.

03: L3 is missing.

Coast/Disable (open
contactor enable relay)
(IAM modules)
Decel/Hold
(AM modules)

Coast/Disable (open
contactor enable relay)
(IAM modules)
Decel/Hold
(AM modules)

FLT S25…PRECHARGE FAILURE

Pre-charge Failure

The converter pre-charge circuit detected that the DC bus did
not reach an appropriate voltage level after charging for a
period of time.

Coast/Disable (open
contactor enable relay)

Coast/Disable (open
contactor enable relay)

FLT S29…SHUNT OVERLOAD FL

Shunt Thermal
Protection

The thermal model for the shunt circuitry indicates that the
temperature has exceeded its rating.

Coast/Disable (open
contactor enable relay)

Coast/Disable (open
contactor enable relay)

FLT S30…SHUNT OVERLOAD UL
(Kinetix 6500 drives only)

Shunt Thermal
Protection

The thermal model for the shunt circuitry indicates that the
temperature has exceeded a user-programmable limit.

Decel/Hold

N/A

FLT S31…SHUNT MODULE

Shunt Module Fault

The shunt module in a multi-axis system has a fault.

Coast/Disable (open
contactor enable relay)

Coast/Disable (open
contactor enable relay)

Advertising