Rockwell Automation Publication 2094-UM002E-EN-P - May 2012

39

Planning the Kinetix 6200 and Kinetix 6500 Drive System Installation

Chapter 2

Establishing Noise Zones

Observe these guidelines when the 2094-BL

xxS or 2094-XL75S-Cx LIM

module is used in the Bulletin 2094 system and mounted left of the IAM module
with the AC (EMC) line filter mounted above the LIM module:

The clean zone (C) is to the right and beneath the Bulletin 2094 system

(gray wireway).

The dirty zone (D) is to the left and above the Bulletin 2094 system, and

above and below the LIM module (black wireway).

The very dirty zone (VD) is from the filter output to IAM module.

Shielded cable is required on the EMC filter (load side) and the braided
shield attached to the clamp provided.

The sercos fiber-optic cables are immune to electrical noise, but due to

their delicate nature, route them in the clean zone. Ethernet cables are
noise sensitive and belong in the clean zone.

Figure 13 - Noise Zones (LIM mounted left of IAM module)

(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway.
(2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the

System Design for Control of Electrical Noise Reference Manual, publication

GMC-RM001

.

C

C

D

VD

D

D

D

D

D

D

VD

D

C

Line Interface Module

Kinetix 6200 or
Kinetix 6500 System

Dirty Wireway

Clean Wireway

Motor Power Cables

Very Dirty Filter/IAM Connections

Segregated (not in wireway)

Fiber-optic Cable

VAC Load

VAC Line

AC Line Filter

(required for CE)

I/O

(1)

, Feedback, and

Ethernet Cables

Route 24V DC switched signals
in shielded cable.

Route encoder, analog, registration, and

communication signals in shielded cables.

I/O

(1)

and Safety Cables

No sensitive

(2)

equipment within

150 mm (6.0 in.).

Advertising