Rockwell Automation Publication 2094-UM002E-EN-P - May 2012

Chapter 2

Planning the Kinetix 6200 and Kinetix 6500 Drive System Installation

When mounting your shunt module inside the enclosure, follow these additional
guidelines:

Mount metal-clad modules anywhere in the dirty zone, but as close to the

Bulletin 2094 drive system as possible.

Route shunt power wires with motor power cables.
Keep unshielded wiring as short as possible. Keep shunt wiring as flat to

the cabinet as possible.

Separate shunt power cables from other sensitive, low voltage signal cables.

Figure 23 - External Shunt Module Inside the Enclosure

C

D

D

D

D

D

VD

C

VD

1394 Digital Servo Controller

300W Shunt Module

BULLETIN 1394 300W SHUNT MODULE

ALLEN-BRADLEY

FOR USE WITH 1394-SJT22-X SYSTEM MODULE

CAT.

PART

SER.

INPUT DC

INPUT AC

FOR FUSE REPLACEMENT USE:

BUSSMAN CAT. NO.

R

D

Line Interface Module

Kinetix 6200 or

Kinetix 6500 System

Dirty Wireway

Clean Wireway

Motor Power Cables

Enclosure

2094-BSP2
Shunt Module

150 mm (6.0 in.)

clearance (min) on all four

sides of the shunt module.

Shunt thermal Switch and Fan Wires (when present)

Very Dirty Connections Segregated

(not in wireway)

Shunt Power Wiring Methods:

Twisted pair in conduit (1st choice).

Shielded twisted pair (2nd choice).

Twisted pair, two twists per foot (min) (3rd choice).

No sensitive

equipment within

150 mm (6.0 in.).

Dirty I/O and

Safety Cables

Clean I/O, Feedback, and

Ethernet Cables