Troubleshooting the Kinetix 6200 and Kinetix 6500 Drive System

Chapter 8

Table 84 - NODE FLT Fault Codes

Four-character
Display Message

RSLogix 5000
Fault Message

Problem or Symptom

Potential Cause

Possible Resolution

NODE FLT 01…LATE CTRL UPDATE
(Kinetix 6500 drives only)

Control Update Fault

Several consecutive updates from the
controller have been lost.

Excessive network traffic.

Remove unnecessary network

devices from the motion
network.

Change the network topology

so that fewer devices share
common paths.

Use faster/higher performance

network equipment.

Noisy environment.

Segregate signal wiring from

power wiring.

Use shielded cables.
Add snubbers to power

devices.

NODE FLT 02…PROC WATCHDOG

Processor Watchdog Fault

The watchdog circuit monitoring processor operation detected a
problem.

Recycle control power or reset

the drive.

Replace control module if

problem persists.

NODE FLT 03…HARDWARE nn

Hardware Fault

The drive has an internal hardware problem. The nn sub-code is defined
as follows:

Recycle control power or reset

the drive.

Replace power module or

power rail if problem persists

01: Invalid slot ID.

Faulty power rail or power
module.

02: Cannot read slot ID.

03: Nonvolatile write to memory

failed.

Faulty memory component.

Recycle control power or reset

the drive.

Replace control module if

problem persists.

04: Nonvolatile memory read failed.

NODE FLT 04…DATA FORMAT
ERROR
(Kinetix 6200 drives only)

Data Format Error

A data format error was discovered in
the controller-to-drive message.

Faulty memory component.

Recycle control power or reset

the drive.

Replace control module if

problem persists.

NODE FLT 06…LOST CTRL CONN
(Kinetix 6500 drives only)

Lost Controller Connection

communication with the controller
have been lost

Faulty Ethernet cable.
Ethernet cable

disconnected.

Check Ethernet connection.

Controller lost power.

Check controller operation.

NODE FLT 08…LOGIC WATCHDOG
(Kinetix 6500 drives only)

Custom Logic Update Timeout

The watchdog circuit monitoring
custom logic operation detected a
problem.

Faulty control module.

Recycle control power or reset

the drive.

Replace control module if

problem persists.

NODE FLT 09…IP ADDRESS
(Kinetix 6500 drives only)

Duplicate IP Address

This drive and another EtherNet device
on the same subnet have identical IP
addresses.

Incorrect node switch
setting.

Select a node address not already
in use on the network.

NODE FLT 128…DRAM TEST

DRAM Test Fault

A power-up test of the DRAM indicated
a memory problem.

Faulty memory component.

Recycle control power or reset

the drive.

Replace Control module if

problem persists.

NODE FLT 129…FPGA CONFIG

FPGA Configuration Fault

The FPGA could not be configured
properly.

Faulty component.

Replace module.

NODE FLT 133…SERCOS ADDRESS
(Kinetix 6200 drives only)

Duplicate Sercos Node Address

This axis and one or more other axes have identical sercos addresses.

Check Node Switch configuration
of all axes on the sercos ring and
adjust for no overlap of addresses.

NODE FLT 139…SERCOS RING
(Kinetix 6200 drives only)

Sercos Ring Fault

The sercos ring is not active after being
active and operational.

Loose or damaged sercos
cable.

Check that fiber-optic cable is
present and connected properly.