Configure and Start the Kinetix 6200 Drive System

4. Determine your source of three-phase input power.

5. Observe the control module four-character status display.

The four-character status display scrolls the node address, then cycles
through phases until final configuration is reached.

6. Observe the status indicators on the front of the control module.

Refer to troubleshooting tables for the Drive, Comm, and Bus status
indicators in Control Module Status Indicators on

page 209

. Refer to the

Kinetix 6000M Integrated Drive-Motor System User Manual, publication

2094-UM003

, for IPIM module and IDM unit status indicator

troubleshooting tables.

7. Observe the three sercos indicators on the Logix sercos module.

If Your Three-phase
Power

Then

Is sourced from a
LIM module

1. Set CB1 to the ON position.
2. Verify the Hardware Enable Input signal for each axis is at 0 volts.

(1)

3. Go to main

step 5

.

(1) The hardware enable input for IDM units is on the IPIM module.

Is not sourced from a
LIM module

1. Apply 324…528V AC (460V) input power to the IAM module (IPD

connector).

2. Verify the Hardware Enable Input signal for each axis is at 0 volts.

(1)

3. Go to main

step 5

.

Four-character Status Indicator

Status

Do This

Scrolling CP-0

The drive is looking for a closed sercos ring (phase 0). Wait for
CONFIGURING or take corrective action.

Check fiber-optic connections.

Scrolling CP-1

The drive is looking for active nodes (phase 1). Wait for CONFIGURING or
take corrective action.

Check node addressing.

Scrolling CP-2

The drive is configuring nodes for communication (phase 2). Wait for
CONFIGURING or take corrective action.

Check program motor and drive configuration against
installed hardware.

Scrolling C O N F I G U R I N G

The drive is configuring device specific parameters (phase 3). When
phase 4 is reached the drive displays the drive state.

Check motor catalog number against selection.

(1)

Scrolling drive state (for example
S H U T D O W N or S T O P P E D)

The drive is configured and active (phase 4).

Go to

step 6

.

Scrolling error code message

Drive is faulted.

Go to

Fault Codes

on

page 198

.

(1) You can get diagnostic information from the module by highlighting the module name in RSLogix 5000 software. A Pseudo Key Failure often indicates that the motor selection does not match the motor

installed.

Three Sercos Indicators

Status

Do This

Flashing green and red

Establishing communication

Wait for steady green on all three
indicators.

Steady green

Communication ready

Go to Test and Tune the Axes on

page 161

.

Not flashing green and red/
not steady green

Sercos module is faulted

Go to the appropriate Logix
manual for specific instructions
and troubleshooting.