Kinetix 6200 and Kinetix 6500 Connector Data

Chapter 4

Control Signal Specifications

This section provides a description of the Kinetix 6200 and Kinetix 6500 drive
I/O (IOD), communication, contactor enable (CED), brake (BC), and control
power (CPD) connectors.

Digital Inputs

Four assignable inputs are available for the machine interface on the control
module. Each IAM and AM module supplies 24V DC @ 200 mA for the
purpose of registration, home, enable, over-travel positive, and over-travel
negative inputs. These are sinking inputs that require a sourcing device. A 24V
DC power and common connection is provided for the digital inputs.

The four digital inputs (IOD-41…IOD-44) have default assignments, however,
you can reassign them according to the needs of your specific application.

Table 25 - Digital Input Default IDN Assignments

You can change the digital input default settings on Kinetix 6200 control
modules by using a sercos IDN Write instruction. For example, digital input 4
(IOD-44) is configured by IDN P-0-055. By default the value is 4 (Registration
2). You can use the sercos IDN Write instruction to change IDN P-0-055 value
to 7, and then digital input 4 is configured as Regeneration OK. Digital input
IDN values are in the table on

page 72

. Refer to Appendix D on

page 271

for

more information on changing default IDN values.

You can change the digital input default settings on Kinetix 6500 control
modules by using RSLogix 5000 software. Refer to

Configure the Drive Modules

on

page 167

for more information on changing default values.

IMPORTANT

To improve registration input EMC performance, refer to the System Design for
Control of Electrical Noise Reference Manual, publication

GMC-RM001

.

IMPORTANT

Over-travel limit input devices must be normally closed.

IOD Pin

Input

IDN

Type

Default

41

1

P-0-052

INT

Enable

42

2

P-0-053

Home

43

3

P-0-054

Registration 1

44

4

P-0-055

Registration 2