Chapter 2

Planning the Kinetix 6200 and Kinetix 6500 Drive System Installation

Observe these guidelines when individual input power components are used in
the Bulletin 2094 system and the Bulletin 2094 LIM module is not used:

The clean zone (C) is beneath the Bulletin 2094 system and includes the

I/O wiring, feedback cable, and DC filter (gray wireway).

The dirty zone (D) is above the Bulletin 2094 system (black wireway) and

includes the circuit breakers, transformer, 24V DC power supply,
contactors, AC line filter, and motor power cables.

The very dirty zone (VD) is limited to where the AC line (EMC) filter

VAC output jumpers over to the IAM module. Shielded cable is required
only if the very dirty cables enter a wireway.

The sercos fiber-optic cables are immune to electrical noise, but due to

their delicate nature, route them in the clean zone. Ethernet cables are
noise sensitive and belong in the clean zone.

Figure 20 - Noise Zones (without LIM module)

(1) If drive system I/O cable contains (dirty) relay wires, route cable in dirty wireway.
(2) When space to the right of the IAM does not permit 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For

examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication

GMC-RM001

.

(3) This is a clean 24V DC available for any device that may require it. The 24V enters the clean wireway and exits to the right.
(4) This is a dirty 24V DC available for motor brakes and contactors. The 24V enters the dirty wireway and exits to the left.

(1)

C

C

D

D

VD

(4)

(3)

D

D

C

Dirty Wireway

Clean Wireway

Motor Power Cables

24V Motor

Brake PS

Circuit

Breaker

XFMR

AC

Line Filter

(required

for CE)

DC

Filter

Contactors

Kinetix 6200 or

Kinetix 6500 System

(2)

(2)

Very Dirty Filter/IAM Connections

Segregated (not in wireway)

I/O

(1)

, Feedback, and

Ethernet Cables

Route 24V DC switched signals
in shielded cable.

Route encoder, analog, registration, and

communication signals in shielded cables.

I/O

(1)

and

Safety Cables

Fiber-optic Cable