Chapter 2

Planning the Kinetix 6200 and Kinetix 6500 Drive System Installation

In this example, the enclosure must have an exterior surface of 6.66 m

2

. If any

portion of the enclosure is not able to transfer heat, it should not be included in
the calculation.

Because the minimum cabinet depth to house the 460V drive (selected for this
example) is 302 mm (11.9 in.), then the cabinet needs to be approximately 2500
mm (high) x 950 mm (wide) x 302 mm (deep).

2 x (0.3 x 0.95) + 2 x (0.3 x 2.5) + 2 x (0.95 x 2.5) = 6.82 m

2

Because this cabinet size is considerably larger than what is necessary to house the
system components, it may be more efficient to provide a means of cooling in a
smaller cabinet. Contact your cabinet manufacturer for options available to cool
your cabinet.

Table 8 - Power Dissipation Specifications

Bulletin 2094 Drive Modules

(1)

Usage as % of Rated Power Output

(watts)

20%

40%

60%

80%

100%

IAM (converter) power module

(2)

2094-BC01-MP5-M

18

21

25

29

34

2094-BC01-M01-M

33

2094-BC02-M02-M

36

44

54

64

75

2094-BC04-M03-M

50

67

87

110

135

2094-BC07-M05-SM

71

101

137

179

226

IAM (inverter) module or AM power module

(2)

2094-BC01-MP5-S or 2094-BMP5-M

46

54

61

69

77

2094-BC01-M01-S or 2094-BM01-M

57

73

90

108

126

2094-BC02-M02-S or 2094-BM02-M

53

72

93

116

142

2094-BC04-M03-S or 2094-BM03-M

94

130

169

211

255

2094-BC07-M05-S or 2094-BM05-M

121

183

252

326

407

Shunt module - 2094-BSP2

68

121

174

227

280

IPIM module - 2094-SEPM-B24-S

To calculate power dissipation for IPIM modules on your 2094 power rail, refer to the Kinetix 6000M Integrated Drive-Motor User
Manual, publication

2094-UM003

.

(1) Power dissipation for the Bulletin 2094 control modules, catalog numbers 2094-SE02F-M00-Sx and 2094-EN02D-M01-Sx, is included in the IAM and AM power module specifications.
(2) Internal shunt power is not included in the calculations and must be added based on utilization.