Rockwell Automation 2094-EN02D-M01-Sx Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drives User Manual User Manual

Page 99

Advertising
background image

Rockwell Automation Publication 2094-UM002E-EN-P - May 2012

99

Connecting the Kinetix 6200 and Kinetix 6500 Drive System

Chapter 5

3. Move the ground jumper.

4. Replace the IAM module front panel and two screws.

Apply 1.6 N•m (14 lb•in) torque.

5. Mount the IAM module back on the power rail.

Refer to Replace Kinetix 6200 and Kinetix 6500 Drive Modules on

page 227

.

Figure 51 - Setting the Ground Jumper (460V IAM power modules)

IAM Module

Configuration

Grounded (default)

Ungrounded

2094-BC01-MP5-M (460V)

P16 and P17

P18 and P19

2094-BC01-M01-M (460V)

2094-BC02-M02-M (460V)

2094-BC04-M03-M (460V)

2094-BC07-M05-M (460V)

P16

P18

P17

(behind P18)

P19

P18

P19

Bottom Screw

Front Panel

(removed)

Ground jumper set

for grounded configuration

(default setting).

Ground jumper set for
ungrounded configuration.

Top Screw

2094-BC01-MP5-M,
2094-BC01-M01-M,
2094-BC02-M02-M,
2094-BC04-M03-M, or
2094-BC07-M05-M
IAM Power Module (460V)

Removable Jumper

IMPORTANT

Use the default jumper setting for grounded power configurations. Move the
jumper, as shown above, for ungrounded power.