Control Module Status Indicators

Table 87 - Drive Status Indicator (sercos control modules)

Table 88 - Comm Status Indicator (sercos control modules)

Table 89 - Bus Status Indicator

Condition

Drive Status

Possible Resolution

Off

No power

Apply power.

Alternating green/red

Self-test (power-up diagnostics)

Wait for steady green.

Flashing green

(1)

Standby (device not configured)

Wait for steady green.

Steady green

Normal operation, no faults

N/A

Flashing red

Minor fault (recoverable)

Refer to four-character fault message.

Steady red

Major fault (non-recoverable)

Refer to four-character fault message.

(1) This condition is the same as sercos ring phases 0, 1, 2, and 3.

Condition

Drive Status

Potential Cause

Possible Resolution

Off

No communication

(1)

Loose fiber-optic connection.

Verify proper fiber-optic cable connections.

Broken fiber-optic cable.

Replace fiber-optic cable.

Receive fiber-optic cable connected to sercos transmit
connector and vice versa.

Check proper sercos fiber-optic cable connections.

Flashing green

(2)

Establishing communication

System is still in the process of establishing sercos
communication.

Wait for steady green indicator.

Node address setting on the drive module does not
match sercos controller configuration.

Verify proper node switch setting.

Steady green

Communication ready

No faults or failures.

N/A

Steady red

No communication

Duplicate node address

Verify proper node addressing. Refer to

Configure the

Drive Modules

on

page 167

.

(1) Refer to Fiber-optic Cable Installation and Handling Instructions, publication

2090-IN010

, for more information.

(2) This condition is the same as sercos ring phases 1, 2, and 3.

Condition

Bus Status

Condition

Off

No power or DC bus is not present.

Normal when bus power is not applied.
Fault exists, refer to

Fault Codes

troubleshooting on

page 198

.

Bus power is present in follower IAM.

Follower IAM power module is not configured as CommonBus Follow in RSLogix 5000 software.
After DC bus voltage is applied, a 2.5 second delay before the indicator begins flashing green is

normal operation to provide the common-bus leader module time to complete pre-charge.

Flashing green

Bus power is present, axis disabled.
No major faults.

Normal when:
24V is not applied to Hardware Enable Input.
MSO instruction is not commanded in RSLogix 5000 software.

Steady green

Bus power is present, axis enabled.
No major faults.

Normal when:
24V is applied to Hardware Enable Input.
MSO instruction is commanded in RSLogix 5000 software.