External Shunt Module
Connections

Follow these guidelines when wiring your external passive shunt module.

Figure 71 - Shunt Module Wiring

Figure 72 - Shunt Module Jumper Settings

(1) These are the default jumper settings.

IMPORTANT

When tightening screws to secure the wires, refer to the tables beginning on

page 102

for torque values.

IMPORTANT

To improve system performance, run wires and cables in the wireways as
established in

Chapter 2

.

Use This
Shunt Module

Cat. No.

With This
Drive Module

Do This

Power rail mounted shunt
module.

2094-BSP2

N/A

Verify the internal shunt jumper is in place between RC-2 and RC-3 (refer to

Figure 72

).

Verify the thermal switch jumper is in place between TS-1 and TS-2 (refer to

Figure 72

).

External passive shunt
module connected to the
power rail shunt module.

1394-SRxxxx

2094-BSP2
Shunt module

Remove the internal shunt jumper between RC-2 and RC-3.
Remove the thermal switch jumper between TS-1 and TS-2

(if your shunt module includes a thermal switch).

Refer to External Shunt Modules on

page 51

for noise zone considerations.

Refer to Shunt Module Wiring Examples on

page 241

.

Refer to the installation instructions provided with your Bulletin 1394 shunt module,

publication

2090-IN004

.

1 2 3

1 2

1 2 3

1 2

COL

INT

DC+

TS2
TS1

COL
INT
DC+

TS2
TS1

External Shunt Resistor

(RC) Connector

Kinetix 6000 Shunt Module, Top View

(catalog number 2094-BSP2)

External Thermal Switch

(TS) Connector

Cable Shield
Clamp

Jumpers