Planning the Kinetix 6200 and Kinetix 6500 Drive System Installation

Chapter 2

Observe these guidelines when installing your Logix platform sercos interface
module:

The clean zone (C) is beneath the less noisy modules (I/O, analog,

encoder, registration, an so forth (gray wireway).

The dirty zone (D) is above and below the power supply and noisy

modules (black wireway).

The sercos fiber-optic cables are immune to electrical noise, but due to

their delicate nature, route them in the clean zone. Ethernet cables are
noise sensitive and belong in the clean zone.

Figure 21 - Noise Zones (ControlLogix chassis)

Cable Categories for Kinetix 6200 and Kinetix 6500 Systems

These tables indicate the zoning requirements of cables connecting to the
Kinetix 6200 and Kinetix 6500 drive components.

Table 10 - IAM Power Module (converter side)

(1)

D

D

C

AC Line

Filter

Spare Slots

Dirty Wireway

Clean Wireway

Route dirty wireways directly above the ControlLogix controller chassis

(shielded by the chassis).

Line Filter/Power Supply

Connections Segregated

(not in wireway)

Dirty I/O

(24V DC I/O, AC I/O)

Clean I/O

(Analog, Encoder

Registration)

Wire/Cable

Connector

Zone

Method

Very
Dirty

Dirty

Clean

Ferrite
Sleeve

Shielded
Cable

CTRL 1 and 2

CPD

X

DC-/DC+ (unshielded cable)

IPD

X

L1, L2, L3 (shielded cable)

X

X

L1, L2, L3 (unshielded cable)

X

CONT EN- and CONT EN+ (M1 contactor)

CED

X