10 Wiring and Installation

23

n/c

n/c

No connection

24

EnOut-

EnOut-

Enable Output (12-24

VDC)

Drv: white/orange

25

EnOut+

Enout+

Drv: orange/white

Encoder Wiring

Quadrature Encoders
The QAx module A, B, and Z inputs accept only Differential Line Driver (RS-422) signals.

Single-ended line drivers (TTL) are not supported due to low noise immunity. The user

must supply power for the encoder.
The Cmn on the QA module must be connected to the encoder, or the signals will not be

read correctly!

Daisy-Chaining A and B Quadrature Inputs
One quadrature encoder can typically output its signals to multiple QA modules. Use a

daisy-chain topology, and add termination only to the last input. Incorrect termination will

result in distorted signals and will cause incorrect transducer readings. Use the Input

Termination Axis Parameter to set the termination. Termination is selectable on the A and

B signals. The Z signal is always terminated with 120 Ω.
RegX/PosLim, RegY/NegLim, and Home Inputs
The Reg/Lim and Home inputs are compatible with signal levels from 12 to 24 V. They

draw 2.7 mA max and turn on when the voltage across the input is greater than 6 V. The

polarity is unimportant.