Fixed Buffer: Receive
Fixed Buffer communication procedure: Procedure Exist
Paring open: Enable
Existence confirmation: Confirm
Host Station Port No.: 7171 hex (29,041 in decimal)
Transmission device IP address: Set this to the IP Address of the

RMC
Transmission target device Port No.: 7171 hex (29,041 in

decimal)
Because Pairing open is set to Enable, the next row will

automatically be set identically, except the Fixed Buffer will be set

to Send. Notice that each QJ71E71-100 can communicate with up

to 8 RMCs.

Opening a Connection on the Q-Series

Before the PLC can communicate with the RMC, the IP connection must be opened using

the ZP.OPEN instruction, described in section 10.8 of the Q Corresponding Ethernet

Interface Module User's Manual (Basic). Both connections of the pair (Send and Receive)

must be opened individually.
The port number must be 7171 hex (29,041 in decimal).

Closing a Connection on the Q-Series

To close the IP connection to the RMC, use the ZP.CLOSE instruction, described in section

10.5 of the Q Corresponding Ethernet Interface Module User's Manual (Basic). Both

connections of the pair (Send and Receive) must be closed individually.

Writing to the RMC with the Q-Series

Use the ZP.BUFSND Instruction to write to registers in the RMC. It is described in section

10.4 of the Q Corresponding Ethernet Interface Module User's Manual (Basic). The RMC

requires that the Send Data of the BUFSND instruction is in the format shown below.

TxCount

(16

bits)

0

(16

bits)

Register

File
(16

bits)

Register
Element
(16

bits)

Data

Item

1

(32

bits)

Data

Item

2

(32

bits)

Data

Item

n

(32

bits)


Description:

TxCount

The number of 16-bit words written, not including this

word.




0

This word must be 0.

Register

File

This is the file number of the register’s address in IEC

format. For example, for %MD8.12, the file number is 8.

Register

Element

This is the element number of the register’s address in IEC

format. For example, for %MD8.12, the element number is

438