Delta RMC151 User Manual

Page 669

Advertising
background image

7 Hardware

Logic 1 (True, On) Low impedance (50 Ω maximum)

Logic 0 (False, Off) High impedance (<1 µA leakage current at 250 V)

Power

Voltage +24 VDC ± 15%

Inrush Current 5A for 150 µs typical

Current - 3 slots Typical 290 mA @ 24 VDC, max 375 mA

4 slots Typical 385 mA @ 24 VDC, max 500 mA
5 slots Typical 485 mA @ 24 VDC, max 625 mA
6 slots Typical 585 mA @ 24 VDC, max 750 mA

DC-DC converter

isolation

500 VAC

Environment

Operating temperature +32 to +140°F (0 to +60°C)

Storage temperature -40 to +185°F (-40 to +85°C)

Humidity 95% non-condensing

Agency compliance CE, UL and CUL. Class I, Division 2 optional.

LEDs

CPU LED

State

Description

Steady Off

No power.

Steady Green

Power is on.

Flashing Green

Updating Flash or a controller restart is pending.

Flashing Red
(Uniform on/off)

The RMC is in the loader. This should occur briefly when the

controller is powered up. If this occurs during normal operation,

an error has occurred in the controller and it must be reset. Cycle

power to the RMC70 to reset it.
Causes:

o

Power Interruption

In certain cases, a power interruption to the RMC may

cause it to go into the loader. Even a very short

interruption, such as 20 msec, can cause problems. This

type of interruption cannot be measured with a standard

multimeter. For accurate power supply verification, use

an oscilloscope or similar high-speed monitoring device.

o

Firmware Bug

Certain firmware bugs will cause the RMC to go into the

loader. If this occurs, and power interruptions have been

ruled out, contact Delta Technical support.

Flashing Red
(Pattern)

The LED will flash 1, 2, or 3 times, pause and then repeat the

pattern. All of these patterns indicate that the RMC failed a self-

test of the RAM subsystem during startup. This is a non-

recoverable major fault. The module will likely need to be shipped

back to Delta for repair.

Steady Red

Non-Recoverable major fault. That is, the module cannot boot at

all, not even into the loader. The module will likely need to be

shipped back to Delta for repair.

RUN LED

deltamotion.com

649

Advertising
This manual is related to the following products: