RMC70/150 and RMCTools User Manual

These sections define two blocks of %MW registers, one for inputs into the PLC

and one for outputs from the PLC. Refer to the manual for your particular

Ethernet module to check how much data is required for the module itself, and

then add the data that will be required by the slave devices.
In our example, we will need 11 incoming registers (produced by the RMC)

and 12 outgoing registers (consumed by the RMC). Because the RMC uses 32-

bit registers and the %MW registers are 16-bit, we need to double each. The

revision of the 140 NOC 711 01 Ethernet module used in this example requires

16 %MW registers each for inputs and outputs in addition to the data

transmitted with slave devices. Therefore the minimum number of inputs are

38 (11x2 + 16) and the minimum number of outputs are 40 (12x2 + 16)

In this example, we set both sizes to 100 to allow room for adding future

devices.