7 Hardware

VC2124 Parallel Outputs
To achieve 200 mA output, wire the two channels in parallel as indicated here:

VC2100
Fuse the ±15 VDC inputs with 5 A maximum, UL-listed, fast-blow fuses. For maximum

protection, use two 500 mA fuses per VC2100.
For noise immunity, use twisted, shielded pairs for all connections (twisted pair with

overall shield is acceptable). For best noise immunity, keep wires from the RMC to the

VC2100 as short as possible and less than 98 ft (30 m), and place ferrites on all cables as

close to the VC2100 as possible. Sample ferrite part numbers from Steward: 28A2029-

0A0 or 0A2, 28A5131-0A2, 28A0593-0A2, 28A0807-0A2, 28A3851-0A2, 28A2024-0A0 or

0A2.