RMC70/150 and RMCTools User Manual

5 Slave Point B (pu)

Any REAL number

6 Endpoint Behavior

Fault (0)

Truncate (1)

Extrapolate (2)

A valid integer as

described.

Description

This command sets up an absolute linear gearing relationship between the master

register and the position target for the axis this command was issued to (the slave axis)

and will make the slave axis follow that relationship. Typically, the master register is the

Target or Actual Position of another axis. This command is very useful for making an axis

follow a reference input (half-axis).
When this command is issued, the slave axis must either already be at the correct point

specified by the relationship based on the current value of the master, or a Transition

command must previously have been issued to specify how the axis should move to get

to the line. Notice that this means most applications will need to use the Transition

command!
Master Point A, Master Point B, Slave Point A, and Slave Point B specify the linear

relationship. The behavior beyond these points depends on the Endpoint Behavior

parameter.

EndPoint Behavior
The Endpoint Behavior specifies what happens to the slave axis if the master moves

outside of the range specified by Master Point A and Master Point B:

Option

Description

Image

Fault

If the master exceeds

either endpoint, the

slave axis' runtime error

bit will be set which will

halt the axis if the Auto

Stops are configured to

do so.

726

Delta Computer Systems, Inc.

Advertising