Delta RMC151 User Manual

Page 578

Advertising
background image

RMC70/150 and RMCTools User Manual

8. Enter a Requested Packet Interval (RPI) between 2.0 and 3200.0 ms in steps of

1.0 ms. The RMC ignores fractions of a millisecond and cannot support an RPI below

2.0 ms. A commonly used RPI is 20.0 ms. Very low RPIs may flood the network.

9. Make sure to check Use Unicast Connection over EtherNet/IP. This option is very

important for reducing network bandwidth required, but is available only in RSLogix

version 18.00.00 and newer.

10. Clear the Inhibit Module check box and set the Major Fault On Controller if

Connection Fails While in Run Mode check box as required by your application.

11. Click Finish.

The above steps will allocate three tags in the Controller Tags database in RSLogix 5000.

These tags correspond to the Input, Output, and Configuration data set up for the module

under the Connection Parameters section above. The type of each tag is a special

module-defined type created by RSLogix. Each special type has a Data field that holds the

actual data. The following table summarizes the tags created for each module:

Tag Name

Type Of

Data

Description

[Name]:I REAL[size]

This is the Input Data, where the Outgoing Cyclic I/O Data

from the Indirect Data in the RMC will appear.
If you selected to use a Sync Register, the first item in this

array is the SyncIn Register, followed by the Indirect

Data[0], Indirect Data[1], and so on:

Tag

With Sync

Register

Without Sync

Register

[name]:I.Data[0] SyncIn Register

Indirect Data [0]

[name]:I.Data[1] Indirect Data [0] Indirect Data [1]
[name]:I.Data[2] Indirect Data [1] Indirect Data [2]
[name]:I.Data[3] Indirect Data [2] Indirect Data [3]

558

Delta Computer Systems, Inc.

Advertising
This manual is related to the following products: