RMC70/150 and RMCTools User Manual

6

Integer Read/Write Register

Bit

Bit Description

31

Read/Write

30

Read/Write Request

16-29 Reserved
15-8

R/W Address File

7-0

R/W Address Element

7

Float*

Explicit Write Value


*These registers are typically REAL data type (floating point), but in some cases may be

DINT or DWORD integers, such as variables declared as such.
Response Block
The Response Block is a block of 8 contiguous 32-bit input registers (cyclic read

registers), corresponding to the Indirect Data Map registers 0 to 7 in the RMC70. These

registers are continuously sent from the RMC70 to the PLC or PC. See Configuring the

Data below for details on setting up this data.
Each of the 8 contiguous input registers always reads from the same register in the

RMC70. However, one of the registers in the Response Block can be set up to return the

value of a read from any single register in the RMC. This allows you to read the value of

any single register at any time. See Read from the RMC70 below.
The Response Block has the following structure:

Register
Number

Data
Type


Description

0

Integer Indirect Data 0 - must be Axis 0 Status bits!

Bit

Bit Description

31

Command Acknowledge

30

Read/Write Acknowledge

0-29 Axis 0 Status Bits

1

Float*

Indirect Data 1

2

Float*

Indirect Data 2

3

Float*

Indirect Data 3

4

Float*

Indirect Data 4

5

Float*

Indirect Data 5

6

Float*

Indirect Data 6

7

Float*

Indirect Data 7

*These registers are typically REAL data type (floating point), but in some cases may be

DINT or DWORD integers, such as variables declared as such.

Configuring the Data

Setting up the Indirect Data Map
The Response Block continuously returns the values from the RMC70 Indirect Data

registers 0-7. These registers, in turn, can be mapped to any registers in the RMC70.

494

Delta Computer Systems, Inc.