Delta RMC151 User Manual

Page 403

Advertising
background image

5 Programming

d. The fourth condition will continuously monitor the discrete input (or variable

register) for moving the axis backward. When it turns "off", it will start User

Program 3, which will stop the axis.

Example 1: Using a "button" on an HMI

The example will follow the method described above.

1. Set up the buttons

First, the user sets up two momentary buttons on the HMI, called Jog Forward and

Jog Back. As with most HMIs, this momentary button can only write to a bit. The

RMC supports writing to bits with the Allen-Bradley DF1 protocol or Modbus/RTU or

Modbus/TCP. This examples shows using DF1. The momentary button writes a "1"

when it is pressed, and a "0" when it is released.
The user programs the Jog Forward button in the HMI to write to bit zero in the

RMC variable 0 (address F56:0/0). In the RMC, the user named this variable

Jog_Forward and defined it as a DINT (double integer).
The user also programs Jog Back button in the HMI is programmed to write to bit

zero in the RMC variable 1 (address F56:1/0). In the RMC, the user named this

variable Jog_Back, and defined it as a DINT type (double integer).
It is very important that these variables be declared as DINT type, because later the

user will use the value of the entire register. If it were a REAL (floating point), it

would be unknown what value it would take on if bit 0 were changed.
After the user has done this, the variable table looks like this:

2. Create three User Programs

The user created three programs. The speeds and accels were chosen based on the

system to be controlled. The user chose positions that are shortly before the end of

the stroke, so if the operator does not release the button, the axis will still stop

before hitting the end.

deltamotion.com

383

Advertising
This manual is related to the following products: