Delta RMC151 User Manual

Page 572

Advertising
background image

RMC70/150 and RMCTools User Manual

Data Table Address: Enter the address of the first Allen-Bradley PLC

register to read RMC registers into, or to write to RMC registers from.
Size in Elements: Enter the number of RMC registers to read or write in this

field.

Target Device: This section holds parameters for the target device.

Message Timeout: Indicate the number of seconds to wait for the RMC to

respond before determining that the attempt failed. This can be set as low

as a few seconds.
Data Table Address: Enter the address of the first RMC register to read or

write in this field. See the Registers Maps topic for help on addresses.
Local / Remote: Choose Local.
Routing Information File (RI): Enter the address in the Routing

Information File that you intend to use (e.g. RI10:0).

3. On the Multi-hop tab, in the To Address box, enter the IP address of the target

RMC. For example, 192.168.0.219.

Using the MSG Block in Ladder Logic
The Allen-Bradley MSG block takes multiple ladder scans to complete. Therefore, it is

important to enable the MSG block for the correct amount of time. Specifically, the MSG

block must be energized until the message control's enable (EN) bit turns on. Delta has

found some aspects of this to be difficult and therefore has provided the following ladder

samples:
Read or Write Continuously

Using the Examine If Open instruction as shown below fulfills two requirements of

continuous MSG transactions. First, it will keep the block energized until the EN turns on,

and second, it de-energizes the MSG block once the transactions is started so that when

the transaction is completed (EN goes low again), the MSG block sees a rising edge on its

input, thus repeating the transaction:

Read or Write Once

This sample takes care to keep the MSG block energized until the MSG block starts, as

indicated by the enable (EN) bit turning on. Once this happens, the application-controlled

TriggerOnce coil is turned off. The message control's Done (DN) or Error (ER) bits can be

used to process the results of the transaction.

552

Delta Computer Systems, Inc.

Advertising
This manual is related to the following products: