Delta RMC151 User Manual

Page 486

Advertising
background image

RMC70/150 and RMCTools User Manual

1

The byte order of multi-byte fields is determined by the Read service selected. For

service 0x4B (Read LSB First), the least-significant byte will be sent first. For service

0x4D (Read MSB First), the most-significant byte will be sent first.

Write (LSB or MSB First) Request:

Offset

Type

1

Size

Field

Name

Description

0

USINT

1

Service

Must be 0x4C (LSB First) or 0x4E (MSB

First).

1

USINT

1

Path Size

Must be 0x02.

2

USINT[4]

4

Path

Must be 0x20 0xC0 0x24 0x01.

6

UINT

2

File

Register file in the RMC to write to.

8

UINT

2

Element

First element in the specified file to write

to.

10

UINT

2

Count

Number of DINTs or REALs to write.

12

DINT or

REAL

4

Register0 Value of first register

16

DINT or

REAL

4

Register1 Value of second register

:

:

:

:

:

12+4xN

DINT or

REAL

4

RegisterN Value of Nth register

1

The byte order of multi-byte fields is determined by the Write service selected. For

service 0x4C (Write LSB First), the least-significant byte must be sent first. For service

0x4E (Write MSB First), the most-significant byte must be sent first.

Write (LSB or MSB First) Response:

Offset Type

Size Field Name

Description

0

USINT

1

Reply Service

Will be 0xCC (LSB First) or 0xCE (MSB

First).

1

USINT

1

Reserved

Will be 0

2

USINT

1

General Status

See below. Zero (0) means success.

3

USINT

1

Additional Status

Size

Will be 0


In the CIP service response, the General Status field can hold one of several values:

Gen

Status Description

0x00

(0)

Success.
The request succeeded.

0x03

(3)

Invalid service data.
This error will occur if the File or Element values are invalid, or for a write, if the

length of the request does not match the expected length based on the Count

value.

0x11

(17)

Reply data too large.
This error will occur if the response generated is too large to be sent. If you

receive this error, you must decrease the Count value for a Read request. The

466

Delta Computer Systems, Inc.

Advertising
This manual is related to the following products: