RMC70/150 and RMCTools User Manual

7. In the Properties - PN-IO (X1) dialog box, select the IO Cycle tab:

Under Update Time, select an update time between 2.0 ms and 512.0 ms. A

commonly-used update time is 16.0 ms.

Under Watchdog Time, the default number of update cycles should typically be

selected, which is 3 in this case.

8. To select the length of the Input Data—which corresponds to the Outgoing Cyclic I/O

Data area in the RMC—expand the Inputs folder in the Hardware Catalog under the

device you added to the PROFINET network, and drag the desired module onto slot 1

in the RMC’s slot view.

Notice that at the time of this writing (September 2010), Siemens S7 PLCs are limited

to 63 input registers.