RMC70/150 and RMCTools User Manual

EtherNet/IP I/O

EtherNet/IP I/O provides a mechanism of deterministically sending data in both directions

between a PLC and remote device. This data is sent on an interval called the Requested

Packet Interval (RPI). The RMC supports a minimum RPI of 2.0 ms to 4.0 ms, depending

on the loop time and number of connections.
EtherNet/IP I/O is a very fast and easy-to-use method of communication. It reduces the

amount of ladder logic required for communication, and communication occurs even when

the PLC is in Program mode.
The RMC supports up to 4 simultaneous EtherNet/IP I/O connections. Only one

connection can be a controlling connection. A controlling connection sends and receives

data with the RMC using the producer-consumer model. The remaining connections must

be input-only, which can only receive data from the RMC. Input-only connections are

rarely used.
The RMC supports only one controlling I/O connection at a time. Therefore, EtherNet/IP

I/O cannot be used simultaneously with a PROFINET IO connection. Other protocols can

be used simultaneously with EthetNet/IP.
EtherNet/IP I/O requires firmware version 2.20 or later.
To learn about setting up and using EtherNet/IP I/O, see the following topics:

Using Allen-Bradley Controllers via EtherNet/IP I/O

Using Omron Controllers via EtherNet/IP I/O

Setting up an EtherNet/IP I/O Connection

Using an EtherNet/IP I/O Connection

EtherNet/IP Messaging

EtherNet/IP explicit messaging allows the originator (PLC or HMI) to request individual

services from the target device (RMC). These requests are made explicitly rather than

being scheduled cyclically like I/O. Explicit messaging is much more flexible than I/O in

terms of what data or services are accessed in the target device, since I/O connections

must pre-configure the I/O data to be exchanged.
In most cases, RMC users use EtherNet/IP Explicit messaging to read and write registers

in the RMC. The RMC provides two methods for doing so. Also, some advanced

EtherNet/IP users may want to access standard CIP services and attributes.
The three types of EtherNet/IP explicit messaging services users may want to use in the

RMC are:

Read and/or write RMC registers using the Allen-Bradley PCCC/DF1 services.

Read and/or write RMC registers using the Data Table Object.

Access standard CIP services and attributes.

See Using EtherNet/IP Explicit Messaging for details on all three.

Supported Number of Connections

The maximum number of each type of connection supported by the RMC75E and

RMC150E is listed below:

Connection Type

Maximum

TCP

64

CIP

32

CIP I/O

4*

*Only one CIP connection can have output data sent from the PLC. The rest must be

Input Only or Listen Only.