6 Communication

Read Rockwell Automation’s EtherNet/IP Performance application guide

(Publication ENET-AP001D-EN-P). It covers this subject in greater detail.

Considerations for RMC EtherNet/IP Performance

The RMC can support EtherNet/IP at its enforced minimum RPIs without compromising its

determinism with respect to motion control or EtherNet/IP I/O communications.

Considerations for Master EtherNet/IP Performance

The PLC EtherNet/IP I/O module must often support a large number of devices, including

RMCs and other devices. Therefore, it is important to recognize the limits in bandwidth of

your EtherNet/IP master controller, and to know how to determine the amount of

bandwidth being utilized. This entire subject is covered in more detail in Rockwell

Automation’s EtherNet/IP Performance application guide (Publication ENET-AP001D-

EN-P), but will be addressed narrowly here for RMC connections.
Here are some published bandwidth limits for EtherNet/IP I/O controllers available as of

this writing:

Manufacturer Module

Total Bandwidth (packets/second)

Allen-Bradley

1756-ENET/B (obsolete) 900

Allen-Bradley

1756-ENBT

5000

Allen-Bradley

1756-EN2T,
1756-EN2TR,
1756-EN2F,
1756-EN2TXT,
1756-EN3TR,

10000

Allen-Bradley

1768-ENBT

5000

Allen-Bradley

1769-L23E

2000

Allen-Bradley

1769-L3xE

4000

Allen-Bradley

1788-ENBT

4000

Schneider Electric Quantum 140 NOC 711 00 7500
Schneider Electric Premium TSX ETC 100

7500

Omron

CS1W-EIP21

6000

Omron

CJ1W-EIP21

6000

Omron

CJ2H-CPUxx-EIP

6000

Omron

CJ2M-CPU3x

3000

Notice that it is recommended that not more than 90% of this bandwidth be used on I/O

connections.
The bandwidth required for each RMC depends on the RPI and the number of connections.

The first connection requires 2 / RPI packets per second (where RPI is in seconds), and

each additional connection requires 1 / RPI additional packets per second. The following

chart summarizes the requirement:

Number of Connections Required Bandwidth (packets/second)
1

2 / RPI

2

3 / RPI

3

4 / RPI

4

5 / RPI


Therefore, to determine the total bandwidth required for any group of RMCs being

serviced by a single master EtherNet/IP I/O controller, simply add up the bandwidth

deltamotion.com

461