Delta RMC151 User Manual

Page 215

Advertising
background image

3 Controller Features

experienced RMC user may not be available.

3. Make more user programs available to the user

If an application requires more user programs than will fit in the RMC, and only a few

user programs are used at any given time, this feature allows splitting up the user

programs between several images. When a certain user program is required, the

respective image is downloaded to the RMC, then the user program can be run.

4. Multiple machine configurations

Some machines need to occasionally change the axis definitions. For example, an axis

may need to use a different feedback input for certain runs. This feature provides a

method of resetting the entire controller configuration in such applications.

Image Size

The size of the image varies based on the specific configuration, especially the amount of user

programming and curves included. The Image Upload/Download supports image sizes up to

65,000 32-bit registers. Typically, the image size is much smaller—on the order of 4,000

registers, unless the controller includes large curves, in which case the image may exceed

65,000 registers, which is not supported by the Image Upload/Download.

Uploading an Image into a PLC

Refer to the Image Area section below for the registers referred to by this procedure.

1. Preparation

Make sure the RMC contains the desired project and that it is saved to Flash.

Verify that the project's IP address and subnet mask are configured correctly,

otherwise communication may be lost after the image is later applied.

Connect the PLC to the RMC via Ethernet.

2. Request the RMC to Build the Configuration Image

The PLC must first request the RMC to construct an image that can be uploaded into

the PLC. This is done by writing Build Upload Image (1) to the Image Area

Command (%MDx.0) register.

3. Wait for the Image to be Built

The RMC may take several seconds to build the requested image. During this time, the

PLC should repeatedly read the Image Area State (%MDx.1) register and wait for

the state to be Upload Image Built (2).

4. Determine the Length of the Image

The length of the image, in 32-bit registers, can now be read from the Image Size

(%MDx.2) register. The PLC can use the contents of this register either to control the

length of the image upload, or to simply verify that the image will fit in the space

provided on the PLC.

5. Read the Image from the RMC Controller

Read the image from the RMC Controller by repeatedly reading from the Image Data

(%MDx.4-…) registers until the entire image has been transferred.

For example, to read a 8000-register image, the PLC could read 4000 registers

twice, starting each read at %MDx.4. Or, if the PLC is limited to 1000 registers per

read, then the PLC could read 1000 registers eight times, again starting each read

at %MDx.4. Both will result in loading the same 8000-register image. The PLC is

responsible for assembling the results from each read into a single image in its

storage area.

The PLC may choose to include the Current Index (%MDx.3) register in each read. This

value can be used to verify that the PLC and RMC agree on the index for the current block

of data.

Downloading an Image from a PLC

Refer to the Image Area section below for the registers referred to by this procedure.

deltamotion.com

195

Advertising
This manual is related to the following products: