Delta RMC151 User Manual

Page 150

Advertising
background image

RMC70/150 and RMCTools User Manual

When overshoot protection is enabled, the velocity is set to zero at each local

minimum/maximum point, which eliminates the chance of the curve overshooting that

point for the curve segments on either side of the point.
For Advanced format curves, Overshoot Protection will not apply to Fixed-Velocity points,

or points at the beginning or end of a Constant-Velocity segment.

Example 1
Consider the cubic curve data in the Endpoint Behavior section above. Without

Overshoot Protection enabled, the curve looks like this:

Notice that the curve overshoots the points after times 0.75, 1.25, and before 1.75.
With overshoot protection enabled, the curve will look like this:

Notice that the curve no longer overshoots the points after times 0.75, 1.25, and

before 1.75. Notice, however, that the curve still overshoots between points 0.25

and 0.5 because neither point is a local minimum or maximum.

Auto-Constant Velocity
The Auto-Constant Velocity option will automatically insert a linear segment in the curve

if three or more data points are in a straight line.
If you have also selected Overshoot Protection, be aware that the points identified as

local minimums or maximums do not count as consecutive points for the Auto-Constant

Velocity (see the example below).
For Advanced format curves, be aware that the Fixed Velocity type points do not count as

consecutive points for the Auto-Constant Velocity (see the example below).

Example 2
Consider the cubic curve data in the Endpoint Behavior section above. The points

at times 0.25, 0.50, and 0.75 are in a straight line, as are the points at times 1.25,

1.50, and 1.75. With the Auto-Constant Velocity option, the curve will look like this:

130

Delta Computer Systems, Inc.

Advertising
This manual is related to the following products: