6 Communication

c.

Add a single tag to the In – Consume tab:

5. i.

Click the In – Consume tab.

ii.

At the bottom of the In – Consume tab, click New.

iii.

In the Edit Tag dialog box, enter the Omron destination tag name in the

Name box, and enter the length of the RMC’s produced data in bytes in the

Size box. This value must be four times the RMC’s 0005 Produced Data

Length device parameter above. Notice that for Omron CS1 and CJ1 PLCs, the

tag name must an Omron address. An address in the H memory range is

recommended to allow direct bit access.