5 Programming

In the RMCTools Options dialog, in the Programming section, you can choose to display

the execution times that RMCTools calculates for the user programs. This can help you

determine what steps are causing problems.
There are several ways of reducing the time usage:

Decrease the number of tasks allocated

This may significantly reduce the worst-case calculations of the time usage.

Assign user programs to tasks

By assigning user programs to only run on certain tasks, or only one task at a time,

you can significantly reduce the worst-case time usage. To assign user programs to

tasks, use the Tasks page on the User Program Properties dialog.

Disable expression logging

This is described in the Reducing the Program Size section above. If your programs

use the Expression (113) command heavily, this may yield a large improvement.

Disable Immediate Command logging

This may significantly reduce the time if your programs use many immediate

commands. To disable immediate command logging, in the Programming Properties

dialog, on the Verify page, uncheck Log Immediate Commands. If this option is

disabled, immediate commands issued from user programs will not be reported in the

Event Log.

Break down complicated steps into multiple smaller steps

When verifying the user programs, the Verify Results window can provide timing

details on the longest steps. Break these into smaller steps.

Use the RMCTools Options dialog to set the Verify Results window to show the timing

details.

Increase the loop time

Increasing the Loop Time will allocate more time for the user programs.

Simplify the programming

In general, the simpler the programming, the less time it takes. Simplifying the

programming may include such things as revisiting your overall programming

approach, or offloading some of the programming to the machine's master controller,

such as a PLC.

Time Allocation

The time allocated for the user programs varies with RMC and the selected loop time. The

time allocated is displayed in the Verify Results window after verifying the programming.

Loop Time

CPU

Firmware

4 ms

2 ms

1 ms 500 µs 250 µs

RMC150E

All

--

1200µs

500/400µs

(note 2)

200µs

(note 1)

75µs

(note

1)

RMC75E

All

3000µs

1200µs

600µs

210µs

75µs

(note

1)

RMC75S

Pre-3.31.0

3000µs

1000µs

500µs

210µs

--

RMC75S

3.31.0+

3000µs

1000µs 500µs/250µs

(note 3)

210 µs

(note 1)

--

RMC75P

Pre-3.31.0

3000µs

1000µs

500µs 210 µs

--

deltamotion.com