E home armed, Home, Armed – Delta RMC151 User Manual

Page 906: Home armed, Home input, E home input, Index (z) wire break

Advertising
background image

RMC70/150 and RMCTools User Manual

Z

Wire

Break

(bit

1)

Z

Input

(bit

0)

Value

of

ZIn

Tag

Description

0

0

0

Z Input On

0

1

1

Z Input Off

1

0

2

Wire Break

Detected

1

1

3

Wire Break

Detected

5

Index (Z) Wire Break

Indicates whether a broken wire is detected

on the quadrature Index (Z) input. Available

only on the RMC70 QAx module.
0=No break
1=Break Detected
In the Axis Tools, the Index (Z) Input status

bit and the Index (Z) Wire Break are

combined into one cell with the values On,

Off, or Break.

All tab:

Home

6

HomeIn

Home Input

Indicates the state of the Home input

(0=Off, 1=On). On the RMC70 QAx and

RMC150 Quadrature (Q) modules, this is the

Home input. On the RMC70 Q1 module, this

is the Reg input. On the Universal I/O

module, this is the corresponding Reg input

on the module. On an SSI incremental axis,

the home input is specified by the SSI Home

Source parameter.
See the Homing topic for more details.

All tab:

Home

7

RegXIn

Reg or RegX/PosLim Input

For the RMC70 Q1 and RMC150 UI/O

modules, indicates the state of the Reg

input. The Reg input is used for

Registration.
For the RMC70 QAx and RMC150 Quadrature

(Q) modules, indicates the state of the

RegX/PosLim input for this axis. The

RegX/PosLim input can be used for

Registration or as a Positive Limit Input.

All tab:

Registration

8

RegYIn

RegY/NegLim Input

Indicates the state of the RegY/NegLim

input for this axis on the RMC70 QAx and

RMC150 Quadrature (Q) modules. The

RegY/NegLim input can be used for

Registration or as a Negative Limit Input.

All tab:

Registration

9

HomeArmed

Home Armed

This bit is set when the Home is armed.

All tab:

Home

886