Delta RMC151 User Manual

Page 1176

Advertising
background image

RMC70/150 and RMCTools User Manual

To minimize electrical interference:

-In and Cmn must be connected. This connected should be made as close to the

transducer as possible.

Use individually shielded twisted-pair wire.

Typically, the cable shield should be connected to earth on one end only.

Current 4-20mA, 2-Wire

Note:

The Analog (G) Module does not support current feedback.

Notes:

The Res and -In pins are internally connected via a 250 Ohm resistor.

To minimize electrical interference, use individually shielded twisted-pair wire.

1156

Delta Computer Systems, Inc.

Advertising
This manual is related to the following products: