Delta RMC151 User Manual

Page 410

Advertising
background image

RMC70/150 and RMCTools User Manual

General Considerations

In a machine fault situation, the following actions are typically desired of the RMC:

1. Halt all the axes

The RMC has several levels of halts.

2. Turn off any Enable Outputs

If any Enable Outputs are wired to a motor drive, or other actuator, these are typically

turned off in a fault situation. The Direct Output Halt will halt the axis and turn off the

axis' Enable Output.

3. Stop User Programs

Any user programs that are running should be stopped to prevent commands from

being issued to the axes.

4. Stop the Program Triggers

The Program Triggers should be stopped to prevent user programs from starting. To

stop the Program Triggers, put the RMC in PROGRAM mode.

5. Turn off discrete outputs

Certain discrete outputs may need to be turned off.

Additional machine considerations:

Blocking Valve

If the RMC halts the hydraulic axis with an Open Loop or Direct Output Halt, the

cylinder may drift. If drifting is unacceptable, install a blocking valve that will close

when the machine faults.

Using the Fault Input to Halt Axes

If the Fault Input Auto Stop is set to a halt, then when the Fault Input becomes active,

that axis will halt, and any new motion will be prevented as long as the Fault Input is

active (except for the Direct Output (9) command). The polarity of the Fault Input can be

set to Active High or Active Low.
Each Fault Input will only halt its corresponding axis. If you want to use the Fault Input

on several axes on the RMC, you will need to wire them all. If you instead want to use

only one discrete input to halt the axes, see the Using a Discrete Input to Halt Axes

section below.
The modules listed below have a Fault Input.

RMC70 RMC150
MA
AA
QA

Quad (Q)


For modules that do not have a Fault Input, you can use a general discrete input to halt

the axes, as described in the Using a Discrete Input section below.
The Fault Input can also be used to put the RMC in PROGRAM mode, thereby stopping all

user programs and the Program Triggers. See the RUN/PROGRAM Mode section below.

Using a Discrete Input to Halt Axes

There are several ways to use a single general discrete input to halt the axes:
Use a single discrete input to halt axes and enter PROGRAM mode
For any axis, you can assign the Positive Limit Input and Negative Limit Input (on any

number of axes) to the same discrete input. If the AutoStops are set to halt on the

Positive Limit Input and Negative Limit Input errors, this will cause the axis to halt when

that discrete input is active. The polarity of the limit inputs can set with the Limit Input

Polarity parameter.

390

Delta Computer Systems, Inc.

Advertising
This manual is related to the following products: