Delta RMC151 User Manual

Page 1161

Advertising
background image

10 Wiring and Installation

I/O 5

Input or Output

I/O 6

Input or Output

I/O 7

Input or Output

Input Cmn Common to one side of all inputs

Discrete Outputs

Each discrete output is a solid state relay (SSR). When it is "OFF", it has high impedance,

and when "ON" it has low impedance (50 Ω maximum, 25 Ω typical). Because the output

is isolated, the user must power it externally. The maximum current and voltage for the

output is 75 mA (50 mA for Class I, Div 2) and 30 V.
Using Outputs with Resistive Loads

Figure 2: SSR switching resistive load: low-side

configuration.

Figure 3: SSR switching resistive load:

high-side configuration.


Example: Calculating maximum current for resitive load.
To calculate the maximum current through the SSR in the above diagram, we assume

zero SSR resistance:

Max. current = 24V / 480Ω = 50mA
Max. current = 12V / 480Ω = 25mA

In the 24V case, the maximum current is right at the maximum allowed by the SSRs. The

outputs may be overpowered if the resistance is reduced further. To calculate the typical

current through the SSR, we use the typical SSR resistance of 25W:
Typical current = 24V / (480Ω + 25Ω) = 47.5mA
Typical current = 12V / (480Ω + 25Ω) = 23.8mA

Using Outputs with Inductive Loads
External fuses should be used to protect the SSRs if there is a possibility of over-

current. When switching inductive loads, it is important to place a diode or tranzorb

across the load to protect the switch when transitioning from an ”ON” to an ”OFF” state.

Otherwise, the collapsing magnetic field can cause a reverse voltage spike in excess of

the 30 V rating of the SSR. See figures below for details.