RMC70/150 and RMCTools User Manual

2. On the Special menu, click Tagname Dictionary, then click New, and do the

following:

a. In the Tagname box, type an name like "Axis0ActPos" (without the

parentheses).

b. Click Type and choose I/O REAL, and click OK.
c. Choose Read Only.
d. Click Access name, choose RMC and click Close.
e. In the Item box, type "404113 F" (without the parentheses). This means it is

looking at a "4" type register at address 4113 (the Modbus address for Axis 0

Actual Position) and it is a Floating-point value.

f. Click Save, then click Close.

aa

3. In an InTouch window, go to the Wizard Selection dialog, choose Value Displays,

choose Analog Tagname Display, and click OK.

4. Place the display on the window, double-click the display, and do the following:

a. In the Tagname box, type "Axis0ActPos" (without the parentheses).
b. In the Number Format box, choose 0.000.
c. Click OK.

5. Click Runtime!
6. The runtime window will display the actual position of the RMC.

Item Address Details using DASMBTCP
All RMC data registers are of Modbus memory type "4".
In the Item box in the Tagname dictionary, adding " F" to the end of the Modbus address

indicates it is a floating-point number. Adding " L" to the end of the Modbus address

indicates it is a 32-bit integer. Adding ":" and then the number, such as "404097:1"

treats it as a discrete, with number after the colon indicating the bit number. Wonderware

counts bits starting at 1.
Calculating RMC Register Addresses
Use the Register Maps to find the Modbus/TCP addresses of the desired registers in the

RMC75E. You can also use the Modbus Addressing topic to easily convert the two-level

addressing to Modbus addresses.