RMC70/150 and RMCTools User Manual

up the PROFIBUS. See the topic for the mode you will be using for parameterization

and configuration values.

3. Configure the PROFIBUS Network

The PROFIBUS network configuration is stored in the master PROFIBUS device.

Creating this configuration is the most difficult step in making the network work.

This step requires a device description file (GSD file) from each device in the

network, including the RMC.
The following steps outline configuring your PROFIBUS-DP network. The steps are

general because various manufacturers handle these steps differently.

1. Open your PROFIBUS-DP master configuration program.
2. If you are modifying an existing PROFIBUS-DP network, open your current

configuration file.

3. If you are creating a new PROFIBUS-DP network, you must create a new

network, add a master device to the network, and select the baud rate of the

network.

4. Add the RMC's GSD file to your configuration programs GSD database if it is

not already there.

5. Add and configure an RMC75P Motion Controller or RMC150E Motion

Controller slave device to the network. This involves selecting the correct

configuration module for your RMC module and application. Refer to Step 2,

Determining the Appropriate GSD Configuration Module, for details on

selecting the correct configuration module.

6. Select the addresses that the master will use for the registers read from the

RMC.

7. The PROFIBUS configuration should include a Word Order setting. Because

PROFIBUS-DP does not specify the word order for 32-bit values, Delta allows

the order to be swapped through this setting. You will probably not know

which is correct until later in the process. If you receive data over the

PROFIBUS network, but the values are not what you expect or do not make

sense, return to this step and try swapping the word order.

8. Add any other RMC devices you want on the same network. To do this, repeat

steps 5, 6 and 7.

9. Save your configuration.
10. Send the configuration to the master device. This step varies greatly

depending on the type of master you use.


If you are using COM PROFIBUS, SyCon, or SST Profibus Configuration, you should

select one of the following topics for more detailed instructions:
Configuring a PROFIBUS-DP Network with COM PROFIBUS
Configuring a PROFIBUS-DP Network with SST Profibus Configuration
Configuring a PROFIBUS-DP Network with SyCon

4. Ready to use PROFIBUS!

Once you have configured the PROFIBUS, can begin the communications. For details

on how to use it, see the topic for the mode you have chosen:
I/O Mode (4, 8, 16, or 32 regs)
Basic (RMC75P only)
Basic+ (RMC75P only)
Enhanced (RMC75P only)
Enhanced+ (RMC75P only)

482

Delta Computer Systems, Inc.