Communications 7-3

1503-UM054C-EN-P – June 2013

If AutoBaud is enabled then the DNet Baud that was selected will be

overridden with the baud rate detected on the network. If no network

activity is detected, then the baud rate will be set to the default baud

rate of 125k.

DeviceNet MACID

The address of the IntelliVAC Plus device shall be settable either

through DeviceNet or through the MACID rotary switches which are

accessible on the side of the IntelliVAC Plus enclosure. These rotary

switches allow an address range of 00 to 99 although only values of

00 to 63 are allowable.


Note:

The data read from the rotary switches must be inverted due

to the operation of the switches.

Rotary Switch

Figure 7.1 – Rotary Switch

Selection of the MACID will be as follows:

‘Set MACID = ‘ ‘00’ to ‘63’

The default MACID shall be set to ‘01’

The MACID setting can be viewed as follows:

‘MACID = ‘ ‘00’ to ‘63’

There shall be a DeviceNet parameter which will allow the MACID

to be set, either from DeviceNet or from the rotary switches. If the

rotary switches do not contain a valid address then the default

address will be used.
The MACID (read-only parameter) selection source setting will be as

follows:

‘MACID Source = ‘ ‘DNet’ or ‘Switches’ default is Dnet