Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 211

Advertising
background image

B-36

Parameters

1503-UM054C-EN-P – June 2013

Table B.6 – DeviceLogix Programs

Bit

Enum Text

Description

0

User customized DeviceLogix

Prog.

Custom Logical operation – DEFAULT

1

FVR DeviceLogix Program

Full Voltage Reversing Starter

2

SMC DeviceLogix Program

Smart Motor Controller

3

RVR DeviceLogix Program

Reduced Voltage Reactor, Non-Reversing

Starter

4

RVAT DeviceLogix Program

Reduced Voltage Auto-Transformer, Non-

Reversing Starter

5

PFCC DeviceLogix Program

Reduced Voltage Auto-Transformer, Non-

Reversing Starter

6

Unused

7

unused

A detailed description of each of the DeviceLogix programs can be

found in Chapter 6.


Configuration of Control Inputs [Control Mask]

Parameter Number:

67,55,43,31,11.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0xB4-1-118

Group:

Control

Units:

-

Minimum Value:

2 = DeviceLogix

Maximum Value:

3 = HIM/PC

Default Value:

2

This parameter allows the user to view, as well as to select, the

Control Mask which defines the source of commands for the

IntelliVAC Plus to use. There are four different sources available

but only two can be selected for a 5 IB MC system. For each of the

Masks listed, a status of ‘0’ indicates that the Mask is disabled and a

status of ‘1’ indicates that the Mask is enabled.

Table B.7 – Control Masks

Bit

Enum Text

Description

0

Local

NOT ALLOWED

1

Network

NOT ALLOWED

2

DeviceLogix

Control from DeviceLogix

3

HIM/PC

Control from HIM/PC

4

Unused

5

Unused

6

Unused

7

Unused

A detailed description of each of the Control masks can be found in

Chapter 9, Logical Masks.