Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 301

Advertising
background image

B-126

Parameters

1503-UM054C-EN-P – June 2013

Trip Coil Open on IB1 [IB 1 Trip Coil Open]
Parameter Number:

243,201,159,117,74.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-1-57

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of Trip Coil Open

fault from the IB1 module. If the bit is ‘0’ then the warning is not

present. If the bit is ‘1’ then the warning is present. See Open Coil

Test in Chapter 4 for a detailed description of this warning.


Trip Coil Open on IB2 [IB 2 Trip Coil Open]
Parameter Number:

244,202,160,118,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-2-57

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of Trip Coil Open

fault from the IB2 module. If the bit is ‘0’ then the warning is not

present. If the bit is ‘1’ then the warning is present. See Open Coil

Test in Chapter 4 for a detailed description of this warning.

Trip Coil Open on IB3 [IB 3 Trip Coil Open]

Parameter Number:

245,203,161,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-3-57

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of Trip Coil Open

fault from the IB3 module. If the bit is ‘0’ then the warning is not

present. If the bit is ‘1’ then the warning is present. See Open Coil

Test in Chapter 4 for a detailed description of this warning.