Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 363

Advertising
background image

C-2

Maintenance

1503-UM054C-EN-P – June 2013

I M P O R T A N T

I M P O R T A N T

The cause of the fuse failure should be
identified before the fuse is replaced otherwise
it may fail again once the IntelliVAC Plus
module is powered up.

RTC Battery

The RTC battery should have a lifetime of at least 10 years so that its

replacement should not be necessary. However, if the RTC should

show to not be operating correctly and resetting the date/time

through RSNetworx does not function correctly, then the battery may

be in need of changing.

I M P O R T A N T

I M P O R T A N T

A properly grounded anti-static strap should
be used at this point.

Begin by removing power to the IntelliVAC unit. To change the

RTC battery (see Fig C.2 below), remove the two screws on the front

of the case and then remove the front section of the enclosure. Next,

remove the three screws that hold the IE circuit board to the IB

circuit board. Carefully remove the IE circuit board (note that there

is a 16 pin connector between the two boards) and place it on a static

free surface. Flip the IE board with the 16 pin connector facing

upwards and remove the battery from its socket and replace it with a

new battery (see Spare Parts list in Appendix C).


Battery Holder

Figure C.2 – Battery Location on Circuit Board

Advertising