Ie operational troubleshooting procedures – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 170

Advertising
background image

Troubleshooting 10-7

1503-UM054C-EN-P – June 2013

Table 10.B - IE Operations Troubleshooting Procedures (cont.)

Plus Status

LED Color

State

Condition/Possible Cause

Corrective Action

Red

7 pulses

Fault

IB1 power loss

Input mains voltage is too low







Failed internal fuse
Faulty IntelliVAC Plus power supply

Check the mains input line and verify that it is greater

than the minimum operating level as defined in the

Electrical Specifications. For proper operation the

input line must be greater than 95Vrms to allow a

contactor to be closed. If the input voltage remains

less than 95Vrms then improvements to the source

must be made. Although the electronics in the

IntelliVAC Plus and IntelliVAC MC units will operate

to a much lower voltage level than 95Vrms, the

contactor will not be able to be closed at such low

levels.
Replace the internal fuse.
Replace the IntelliVAC Plus module.

Red

8 pulses

Fault

Coil open

Contactor coil connections faulty

Faulty coil

Contactor coil connections faulty on

other MC units

Faulty coils on other MC units

Faulty IntelliVAC Plus unit

Faulty IntelliVAC MC unit(s)

Check the connections between the IntelliVAC Plus

and the contactor.

Check the resistance of the coil and confirm that it is

in the range.

Check the connections between the other IntelliVAC

MC units and their contactors.

Check the resistance of the coils controlled by other

IntelliVAC MC units and confirm that they are in the

range.

Replace the IntelliVAC Plus unit.

Replace other IntelliVAC MC unit(s).

IE Operational Troubleshooting Procedures

The following table identifies possible causes and corrective actions

when troubleshooting IE related faults using the IntelliVAC Plus 7-

Segment LED Display.

Table 10.C – IE Operational Trouble Shooting Procedures

7-Segment

Display

State

Condition/Possible Cause

Corrective Action

‘-1’

solid

Fault

RS485 Incorrect duplicate address(es)

Incorrect Address(es) selected

Invalid address(es) selected

Duplicate address(es) selected

Incorrect R

TERM

selected

In an IntelliVAC MC system, the correct number of

addresses has not been selected. Set the additional

IntelliVAC MC addresses to 2,3,4 or 5 only.

In an IntelliVAC MC system, invalid addresses have

been selected. Set the additional IntelliVAC MC

address to 2,3,4 or 5 only. Addresses 0,1,6 and 7 are

not valid for the additional IntelliVAC MC units.

In an IntelliVAC MC system, there can be no

duplication of addresses. Addresses 2,3,4 or 5 can

only be used by one individual IntelliVAC MC unit.

In an IntelliVAC MC system, an incorrect R

TERM

resistor on only the last IntelliVAC MC unit in an

IntelliVAC MC system.