Appendix c_maintenance, Appendix, Maintenance – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 362

Advertising
background image

Appendix

C

1503-UM054C-EN-P – June 2013

Maintenance



Introduction

The IntelliVAC Plus product has is a very robust device which

contains only two user serviceable parts. These parts are:

the fuse for the mains input line and

the battery used by the Real Time Clock (RTC) circuitry.

Mains Input Fuse

This fuse is designed to protect the IntelliVAC Plus unit in the event

of the failure of a contactor coil or failure of an internal electronic

component. If power is applied to the mains input at TB1-2 and the

unit does not respond then the problem may be that the input fuse has

failed.

I M P O R T A N T

I M P O R T A N T

A properly grounded anti-static strap should
be used at this point.

Begin by removing power to the IntelliVAC unit. To change the

fuse (see Fig C.1 below), remove the two screws on the front of the

case and then remove the front section of the enclosure. Next,

remove the three screws that hold the IE circuit board to the IB

circuit board. Carefully remove the IE circuit board (note that there

is a 16 pin connector between the two boards) and place it on a static

free surface. Now remove the fuse on the lower right side of the IB

module and replace it with a new fuse (see Spare Parts list in

Appendix C).


Fuse

Figure C.1 – Fuse Location