Data table layout, Table e.29 shows the data table layout – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 381

Advertising
background image

E-16

DeviceNet Information

1503-UM054C-EN-P – June 2013

Data Table Layout

Table E.29 shows the data table layout.

Table E.29 – DeviceLogix Data Table Layout

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

NUMBER_OF_HARDWARE_OUTPUTS_BYTES (O~7) = 1 byte

Byte 0

---

---

---

---

---

---

OutB

OutA

NUMBER_OF_HARDWARE_INPUT_BYTES (8~f) =1 byte

Byte 1

IE-In7

IE-IN6

IE-In5

IE-In4

IE-In3

IE-In2

IE-In1

IE-In0

NUMBER_OF_CONSUMED_NETWORK BYTES (10~1F) = 1 byte

Byte 2

CNB7

CNB6

CNB5

CNB4

CNB3

CNB2

CNB1

CNB0

Byte 3

CNB15

/Net Jog

CNB14

/Net REV

CNB13

/Net FWD

CNB12

/Net Stop

CNB11

/Net Start

CNB10

CNB9

CNB8

NUMBER_OF_PRODUCED_NETWORK_BYTES (20~3F) = 4 bytes

Byte 4

PNB7

/Interim 5

PNB6

/Interim 4

PNB5

/Interim 3

PNB4

/Interim 2

PNB3

/Interim 1

PNB2

PNB1

PNB0

/Reset All Fault

Byte 5

PNB15

/Test mode

status

PNB14

/Normal

mode status

PNB13

/Local mode

status

PNB12

/Remote

mode status

PNB11

/Isolation

status

PNB10

/Speed SW

REV status

PNB9

/Speed SW

FWD status

PNB8

/protection

status

Byte 6

PNB23

/IB4-OutB

PNB22

/IB4-OutA

PNB21

/IB3-OutB

PNB20

/IB3-OutA

PNB19

/IB2-OutB

PNB18

/IB2-OutA

PNB17

/IB1-OutB

PNB16

/IB1-OutA

Byte 7

PNB31

/Jog tag

PNB30

/REV tag

PNB29

/FWD tag

PNB28

/Stop tag

PNB27

/Start tag

PNB26

/Stop status

tag

PNB25

/IB5-OutB

PNB24

/IB5-OutA

NUMBER_OF_MISCELLANEOUS_BYTES (40~77) = 7 bytes

Byte 8

IB3-In1

IB3-In0

IB2-In2

IB2-In1

IB2-In0

IB1-In2

IB1-In1

IB1-In0

Byte 9

Stop Status

IB5-In2

IB5-In1

IB5-In0

IB4-In2

IB4-In1

IB4-In0

IB3-In2

Byte 10

Start Ready

Status*

Interim 2

Interim 1

IO_CONXN_

IDLE

IO_CONXN_

FLT

IO_CONXN_

OK

EXP_CONXN_

FLT

EXP_CONXN_

OK

Byte 11

Interim 5

Interim 4

Interim 3

Jog

REV

FWD

Stop

Start

Byte 12

Test mode

status

Normal

mode status

Local mode

status

Remote

mode status

Isolation SW

status

Speed SW

REV status

Speed SW

FWD status

Protection

status

Byte 13

IB4 OutB

IB3 OutA

IB3 OutB

IB3 OutA

IB2 OutB

IB2 OutA

IB1 OutB

IB1 OutA

Byte 14

---

---

---

---

---

Fault

Status**

IB5 Out B

IB5 OutA

NUMBER_OF_FUNCTION_BLOCK_OUTPUT_BYTES (78~C7) = 10 bytes

Byte 15

FB7

FB6

FB5

FB4

FB3

FB2

FB1

FB0

Byte 16

FB15

FB14

FB13

FB12

FB11

FB10

FB9

FB8

Byte 17

FB23

FB22

FB21

FB20

FB19

FB18

FB17

FB16

Byte 18

FB31

FB30

FB29

FB28

FB27

FB26

FB25

FB24

Byte 19

FB39

FB38

FB37

FB36

FB35

FB34

FB33

FB32

Byte 20

FB47

FB46

FB45

FB44

FB43

FB42

FB41

FB40

NUMBER_OF_FUNCTION_BLOCK_OUTPUT_BYTES (78~C7) = 10 bytes

Byte 21

FB55

FB54

FB53

FB52

FB51

FB50

FB49

FB48

Byte 22

FB63

FB62

FB61

FB60

FB59

FB58

FB57

FB56

Byte 23

FB71

FB70

FB69

FB68

FB67

FB66

FB65

FB64

Byte 24

FB79

FB78

FB77

FB76

FB75

FB74

FB73

FB72