Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 218

Parameters B-43
1503-UM054C-EN-P – June 2013
Enabling of the AutoBaud Rate Feature [Autobaud Enable]
Parameter Number:
79,67,55,43,30.
Access rule:
Get/Set
Data Type:
BOOL
Object Mapping:
0xB4-1-15
Group:
Communication
Units:
-
Minimum Value:
0 = Enabled
Maximum Value:
1 = Disabled
Default Value:
0
This parameter allows the user to view and set the AutoBaud Rate
Enable feature. If it is enabled then the baud rate will be set by the
network traffic rate, if network traffic is found. If it is disabled, then
the Baud rate will be set by the DeviceNet Baud Rate parameter #76.
Produced IO Bit Size [Produced IO Size]
Parameter Number:
80,68,56,44,31.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0xB4-1-23
Group:
Communication
Units:
-
Minimum Value:
1
Maximum Value:
7
Default Value:
7
This parameter allows the user to view the size (in bytes) of the
Produced IO.
Consumed IO Bit Size [Consumed IO Size]
Parameter Number:
81,69,57,45,32.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0xB4-1-24
Group:
Communication
Units:
-
Minimum Value:
1
Maximum Value:
3
Default Value:
3
This parameter allows the user to view the size (in bytes) of the
Consumed IO.