Parameters B-79

1503-UM054C-EN-P – June 2013

Delay Restart Wait Time for IB2
[IB 2 Delay Restart Wait Time]

Parameter Number:

144,122,100,78,_.

Access rule:

Get

Data Type:

UINT

Object Mapping:

0x384-2-20

Group:

Configuration

Units:

Seconds

Minimum Value:

0

Maximum Value:

3600

Default Value:

0

This parameter allows the user to view the Delay Restart Wait Time

for IB2. It shows the time left, as a constantly updated real time,

after the contactor has closed, before it is permitted to close again.

This parameter works in conjunction with parameter #139 which

defines the minimum time allowed between successive closings of

contactor IB2. See Delayed Restart in Chapter 4 for a more detailed

description of this feature.


Delay Restart Wait Time For IB3
[IB 3 Delay Restart Wait Time]

Parameter Number:

145,123,101,_,_.

Access rule:

Get

Data Type:

UINT

Object Mapping:

0x384-3-20

Group:

Configuration

Units:

Seconds

Minimum Value:

0

Maximum Value:

3600

Default Value:

0

This parameter allows the user to view the Delay Restart Wait Time

for IB3. It shows the time left, as a constantly updated real time,

after the contactor has closed, before it is permitted to close again.

This parameter works in conjunction with parameter #140 which

defines the minimum time allowed between successive closings of

contactor IB3. See Delayed Restart in Chapter 4 for a more detailed

description of this feature.