Trip Coil Open on IB4 [IB 4 Trip Coil Open]
Parameter Number:

246,204,_,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-4-57

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of Trip Coil Open

fault from the IB4 module. If the bit is ‘0’ then the warning is not

present. If the bit is ‘1’ then the warning is present. See Open Coil

Test in Chapter 4 for a detailed description of this warning.


Trip Coil Open on IB5 [IB 5 Trip Coil Open]
Parameter Number:

247,_,_,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-5-57

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of Trip Coil Open

fault from the IB5 module. If the bit is ‘0’ then the warning is not

present. If the bit is ‘1’ then the warning is present. See Open Coil

Test in Chapter 4 for a detailed description of this warning.

Extended Close Time on IB1 [IB 1 Extended Pick up Time]

Parameter Number:

248,205,162,119,75.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-1-55

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of Extended Pick

up Time warning

from the IB1 module. If the bit is ‘0’ then the

warning is not present. If the bit is ‘1’ then the warning is present.

See Contactor Close Time, Extended Close Time & Tables 4.F &

4.G in Chapter 4 for a detailed description of this warning.