Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 96

Advertising
background image

Wiring (MC) 6-9

1503-UM054C-EN-P – June 2013

Incomplete Sequence Timer

The Incomplete sequence timer is designed to ensure that the duty

cycle of the reactor is not exceeded in a single start. It controls the

maximum amount of time which the unit will pass current through

the reactor. If a transition to full voltage has not been made before

the incomplete sequence timer expires the start will be aborted, and

the unit will be locked from beginning another start until it is

manually reset using the reset push button.

Default setting: 15 Seconds

Transition Timer

The Transition Timer controls the amount of time the starter will

provide reduced voltage to the motor. When this timer expires the

run contactor will close which will bypass the reactor and provide

full voltage to the motor.

Default setting: 10 Seconds