Description of Features 4-39

1503-UM054C-EN-P – June 2013

Application Programming Error – CRC

This is a Fault condition which indicates that the Application

Firmware being programmed into the internal Flash did not program

correctly. This error was detected by way of the CRC from the

programmed memory not corresponding to the CRC of the original

source file. The only functionality that the IntelliVAC Plus has is

that it will run the BootLoader firmware and send out the menu over

the RS485 link at a 9600 baud rate to a PC. Another attempt can

now be made to Flash the IntelliVAC Plus unit again.

The Plus status LED is pulsing Red with a pattern of 5 pulses.

RS485 Communications Fault (IB Fault)

This is a Fault condition which indicates that the one or more of the Basic

units connected, has an RS485 communications error. This may be the

Basic unit contained in the IntelliVAC Plus or one of the Basic units in an

IntelliVAC MC module. When this error occurs, proper operation of the

IntelliVAC Plus or IntelliVAC MC system is no longer possible.

The Plus status LED is pulsing Red with a pattern of 6 pulses.

IB1 Power Loss

This is a Fault condition which indicates that the Basic module,

within the IntelliVAC Plus, has lost its internal DC power. Because

of this, the Basic module is not operational so that contactor control

cannot be performed. The reason for the loss of the Basic module

power may be due to loss of the main input power or because of a

faulty internal power supply.

The Plus status LED is pulsing Red with a pattern of 7 pulses.

Coil Open

This is a Fault condition which indicates that there are one or more

open contactor coils. The fault monitors both the main coil(s) in an

electrically held contactor or the close and trip coils in a

mechanically latched contactor.

The Plus status LED is pulsing Red with a pattern of 8 pulses.