8-14

Configuration/Programming

1503-UM054C-EN-P – June 2013

Upon completion of the transfer the transfer dialog box will

disappear. The CRC of the new firmware file will be calculated and

displayed. If the CRC is good an “OK” will appear beside the CRC

and the user will be prompted for input. Pressing any key on the

keyboard will return the user to the bootloader main menu.



Figure 8.10 - Transfer complete


Power on Reset IntelliVAC

The power on reset option allows the user to restart the IntelliVAC

unit without removing power. This allows the user to keep the hyper

terminal window open and observe the boot up sequence. The

correct boot up sequence for a unit with valid firmware is to display

the bootloader menu for a period of approximately 1 second then run

the application code. The user can determine when the application

code is running by observing the Module status LED. The module

status LED is orange when in bootloader mode and green when the

application code is running.

Updating IntelliVAC Plus Application Code

The most common method of updating the application code of the

IntelliVAC Plus module is using a DeviceNet connection to the

module, and Control flash software. Alternatively the firmware can

be updated using RS-485 interface similar to the IntelliVAC base

module.