Devicenet troubleshooting procedures – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 173

Advertising
background image

10-10

Troubleshooting

1503-UM054C-EN-P – June 2013

Table 10.D – MC Operational Troubleshooting Procedures

7-Segment

Display

State

Condition/Possible Cause

Corrective Action

Off

Normal

No input power on the mains input

Input mains voltage low

Input mains connections faulty

Failed internal fuse

Check that the mains input voltage, on the IntelliVAC

MC unit is within the operating voltage range defined

in the Electrical Specification.

Check the connections to the mains input voltage.

If the mains input voltage is present, check the

internal fuse.

Off

Fault

Invalid MC address selected

MC address is invalid

Set the MC address to either 2,3,4 or 5. Addresses

0,1,6 or 7 are invalid and will not be displayed on the

7-segment LED display of the IntelliVAC MC module.

DeviceNet Troubleshooting Procedures

The following table identifies possible causes and corrective actions

when troubleshooting IE related faults using the DeviceNet Network

Status LED.

Table 10.E – DeviceNet Troubleshooting Procedures

Network

Status LED

Color

State

Condition/Possible Cause

Corrective Action

Off

Normal

There is no power from the mains input

or from DeviceNet.

1. Low input mains voltage

2. Input mains connections faulty

3. DeviceNet connections faulty

4. No/low DeviceNet input power

5. No/low DeviceNet input power and

mains input power present

Check that the mains input voltage is within the

operating voltage range defined in the Electrical

Specification.

Check the connections to the mains input voltage.

Check the DeviceNet connections.

Check that the DeviceNet input power (if present) is

within the operating voltage range defined in the

Electrical specification.

If there is no DeviceNet power and the mains input

voltage is present, check the internal fuse.

Green

flashing

Warning

Determining network baud rate

1. IntelliVAC Plus is on-line but not

allocated to a master.

Check DeviceNet master and its scan list for correct

scanner configuration.

Green

flashing

Warning

On-line but not allocated to master.

IntelliVAC Plus is on-line but not

allocated to a master.

Check DeviceNet master and its scan list for correct

scanner configuration.

Green

solid

None

Normal operation and allocated to master

1. No action required

Red

flashing

Warning

I/O connection timed-out

Reset DeviceNet master device.

Red

solid

Fault

Bus Off or Duplicate address or Invalid

baud

Diagnostics test failed on power-up reset.

Internal fault exists.

Duplicate DeviceNet node address exists

(two DeviceNet nodes cannot have the

same address).

Invalid baud rate (if autobaud is disabled).

Cycle power to the unit and network. If the fault still

exists, replace the IntelliVAC Plus unit.

Change the value of Parameter 57, NonVol MAC ID,

to a valid address and reset the device.

This will only occur if Parameter 55,

AutoBaudEnable, is set to ‘disabled’. Set Parameter

55 to ‘enabled’ and reset the IntelliVAC Plus unit or

set Parameter 56, NonVol Baud Rate, to the correct

setting and reset the IntelliVAC Plus unit.